BF-2226-2

System details

Type
Service Penetration
Element
Wall
Substrate
Double Layer
Minimum Substrate Thickness
118 mm
FRL / FRR
-/90/90
Trade
Plumbing / Hydraulic / Active Fire
Service
PEX
Fire Rating
90

Fire-stopping products

BF-2226-2 system drawing

Application dimensions

Service Diameter Range
20 mm
Aperture
30 mm
Annular Gap
4.5 - 6 mm
Sealant Depth
13 mm
Sealant Fillet
0 mm

Specimen size & details

**Specimen achieved greater perfromance, but the FRL is limited to the published perfromance of the wall.**
20 mm PEX pipe (AUSPEX PE-Xb pipe). HPE installed into the annular gap, 13 mm deep finished flush both sides.