BF-2230-1
System details
- Type
- Service Penetration
- Element
- Wall
- Substrate
- Single Layer
- Minimum Substrate Thickness
- 118 mm
- FRL / FRR
- -/90/90
- Trade
- Electrical
- Service
- Mixed Bundle
- Fire Rating
- 90
Fire-stopping products
Application dimensions
- Aperture
- 26 mm
- Annular Gap
- 4 - 5.5 mm
- Sealant Depth
- 13 mm
- Sealant Fillet
- 0 mm
Specimen size & details
**Specimen achieved greater perfromance, but the FRL is limited to the published perfromance of the wall.**
Cable bundle 2 x CAT6, 2 x COAX, 1 x Security cable. HPE installed into the annular gap, 13 mm deep finished flush.