BF-2363-4

System details

Type
Service Penetration
Element
Wall
Substrate
Concrete
Minimum Substrate Thickness
118 mm
FRL / FRR
-/60/60
Trade
Plumbing / Hydraulic / Active Fire
Service
Plastic Pipes, UPVC
Fire Rating
60

Fire-stopping products

BF-2363-4 system drawing

Application dimensions

Min Diameter
0 mm
Max Diameter
40 mm
Service Diameter Range
Up to 40 mm
Aperture
Up to 1200 x 500 mm
Annular Gap
5 mm
Sealant Depth
Depth of collar mm
Sealant Fillet
0 mm

Specimen size & details

Up to 40 mm uPVC pipe with 5.0 mm wall thickness, penetrating 2 layers of BOSS Batt™ protecting an aperture up to 1200 mm x 500 mm. The system includes a 40 mm BOSS MaxiCollar™ installed to both sides. Sealant installed in the gap between the collar and pipe to full depth. Maximum 5 mm annular gap through substrate. Installed in min 118 mm thick walls.