BF-2772-4

System details

Type
Service Penetration
Element
Wall
Substrate
Concrete
Minimum Substrate Thickness
118 mm
FRL / FRR
-/60/30
Trade
Plumbing / Hydraulic / Active Fire
Service
PEX
Fire Rating
60

Fire-stopping products

BF-2772-4 system drawing

Application dimensions

Min Diameter
0 mm
Max Diameter
25 mm
Service Diameter Range
Up to 25 mm
Aperture
Up to 1200 x 500 mm
Annular Gap
2.5 mm
Sealant Depth
Depth of collar mm

Specimen size & details

Up to 25 mm PEX pipe with 6.2 mm wall thickness, penetrating 2 layers of BOSS Batt™ protecting an aperture up to 1200 mm x 500 mm. Sealant installed in the gap between the collar and pipe to the full depth of the collar, finished flush both sides. The system includes a 40 mm BOSS MaxiCollar™ installed to both sides.

Resources