BF-2774-7

System details

Type
Service Penetration
Element
Wall
Substrate
AAC / Hebel 
Minimum Substrate Thickness
144 mm
FRL / FRR
-/120/60
Trade
Plumbing / Hydraulic / Active Fire
Service
PEX
Fire Rating
120

Fire-stopping products

BF-2774-7 system drawing

Application dimensions

Min Diameter
0 mm
Max Diameter
25 mm
Service Diameter Range
Up to 25 mm
Aperture
Up to 1200 x 500 mm
Annular Gap
3.5 mm
Sealant Depth
Depth of collar mm

Specimen size & details

Up to 25 mm PEX pipe with 3.1 mm wall thickness, penetrating 2 layers of BOSS Batt™ protecting an aperture up to 1200 mm x 500 mm. Sealant installed in the gap between the collar and pipe to the full depth of the collar, finished flush both sides. The system includes a 32 mm BOSS MaxiCollar™ installed to both sides.