BF-2853-33

System details

Type
Service Penetration
Element
Floor
Substrate
Cross Laminated Timber (CLT)
Minimum Substrate Thickness
200 mm
FRL / FRR
-/120/120
Trade
Plumbing / Hydraulic / Active Fire
Service
Plastic Pipes, UPVC
Fire Rating
120

Fire-stopping products

BF-2853-33 system drawing

Application dimensions

Min Diameter
0 mm
Max Diameter
50 mm
Service Diameter Range
Up to 50 mm
Annular Gap
12.5 mm
Sealant Depth
5 mm

Specimen size & details

Up to 50 mm uPVC DWV pipe with 2.7 mm maximum wall thickness. BOSS FireMastic-300™ sealant is used to the top side and BOSS FireMastic-HPE™ sealant is used to the underside. Sealant 5.0 mm deep in 12.5 mm annular gap both sides. 50 mm BOSS MaxiCollar™ installed on the underside.

Resources