BF-2887-12
System details
- Type
- Service Penetration
- Element
- Wall
- Substrate
- Shaftliner
- Minimum Substrate Thickness
- 100 mm
- FRL / FRR
- -/90/90
- Trade
- Plumbing / Hydraulic / Active Fire
- Service
- Plastic Pipes, UPVC
- Fire Rating
- 90
Fire-stopping products
Application dimensions
- Min Diameter
- 0 mm
- Max Diameter
- 110 mm
- Service Diameter Range
- Up to 110 mm
- Aperture
- Up to 600 x 600 mm
- Annular Gap
- 6 mm
Specimen size & details
Up to 110 mm uPVC pipe with 5.2 mm wall thickness. The system penetrated 2 layers of BOSS Batt™ friction fitted and bedded in a 600 mm x 600 mm aperture. All edges sealed with BOSS FireMastic-300™ sealant. 4 layers of BOSS UniWrap™ or BOSS PWP Pipe Wrap flush with the face of the separating element on both sides installed in the 6.0 mm annular gap. Sealant applied to the ends of the BOSS UniWrap™ or BOSS PWP Pipe Wrap on both sides with BOSS FireMastic-HPE™.