BF-2959-18

System details

Type
Service Penetration
Element
Wall
Substrate
Pronto Panel (w/Buildup) 
Minimum Substrate Thickness
118 mm
FRL / FRR
-/60/30
Trade
Plumbing / Hydraulic / Active Fire
Service
CPVC
Fire Rating
60

Fire-stopping products

BF-2959-18 system drawing

Application dimensions

Min Diameter
0 mm
Max Diameter
50 mm
Service Diameter Range
Up to 50 mm
Annular Gap
5 mm
Sealant Depth
Depth of collar mm

Specimen size & details

Up to 50 mm cPVC pipe with 10.1 mm wall thickness. The system includes a 50 mm BOSS MaxiCollar™ installed to both sides. Sealant installed in the gap between the collar and pipe to full depth. Maximum 5 mm annular gap through substrate. Installed in min 118 mm thick walls.