Type
Service Penetration
Element
Wall
Substrate
Masonry
Minimum Substrate Thickness
78 mm
FRL / FRR
-/240/60
Trade
Plumbing / Hydraulic / Active Fire
Service
Plastic Pipes, UPVC
Fire Rating
240

Fire-stopping products

BF-3098-5 system drawing

Application dimensions

Min Diameter
0 mm
Max Diameter
110 mm
Service Diameter Range
Up to 110 mm
Annular Gap
2.5 mm
Sealant Depth
10 mm
Sealant Fillet
5 mm

Specimen size & details

Up to 110 mm uPVC DWV pipe with 3.5 mm wall thickness. FM-300 sealant installed around service 10 mm deep in annular gap finished flush both sides. FM-HPE sealant was also applied as a 5 mm fillet on the joint between the collar and panel both sides. The system includes a 150 mm BOSS MaxiCollar™ installed to both sides.