BF-3213-33

System details

Type
Service Penetration
Element
Floor
Substrate
Cross Laminated Timber (CLT)
Minimum Substrate Thickness
200 mm
FRL / FRR
-/120/120
Trade
Plumbing / Hydraulic / Active Fire
Service
Plastic Pipes, UPVC
Fire Rating
120

Fire-stopping products

BF-3213-33 system drawing

Application dimensions

Min Diameter
40 mm
Max Diameter
40 mm
Service Diameter Range
40 mm
Aperture
50 mm
Sealant Depth
5 mm

Specimen size & details

40 mm uPVC DWV pipe. BOSS FireMastic-300™ sealant 5.0 mm deep in annular gap on the top side. BOSS FireMastic-HPE™ sealant 5.0 mm deep in annular gap on the underside. 40 mm BOSS MaxiCollar™ installed on the underside.

Resources