BF-3274-2

System details

Type
Service Penetration
Element
Wall
Substrate
Double Layer
Minimum Substrate Thickness
118 mm
FRL / FRR
-/60/0
Trade
Plumbing / Hydraulic / Active Fire
Service
Copper Pipe
Fire Rating
60

Fire-stopping products

BF-3274-2 system drawing

Application dimensions

Min Diameter
50 mm
Max Diameter
50 mm
Service Diameter Range
50 mm
Aperture
65.1 mm
Annular Gap
4.8 - 7.1 mm
Sealant Depth
13 mm

Specimen size & details

50 mm copper pipe with 1.9 mm wall thickness. BOSS FireMastic-300™ sealant 13 mm deep in annular gap finished flush both sides.