BF-3293-28

System details

Type
Service Penetration
Element
Floor
Substrate
Comflor
Minimum Substrate Thickness
130 mm
FRL / FRR
-/120/120
Trade
Electrical
Service
TPS
Fire Rating
120

Fire-stopping products

BF-3293-28 system drawing

Application dimensions

Aperture
76 mm
Annular Gap
11.5 mm
Sealant Depth
Top 5 Bottom 25 mm

Specimen size & details

Bundle of 22 x 2.5 mm², 2C+E TPS Power Cables. 270 mm x 270 mm section of BOSS Batt™ installed to the underside of the floor system, with the gap between the BOSS Batt™ and the top rib filled with a trapezoid shape section of BOSS Batt™. BOSS FireMastic-HPE™ sealant to depth of 5 mm on the top side finished flush. BOSS FireMastic-HPE™ 25 mm deep in the annular gap on the underside finished flush.

Resources