BF-3361-2

System details

Type
Service Penetration
Element
Wall
Substrate
Double Layer
Minimum Substrate Thickness
116 mm
FRL / FRR
-/120/120
Trade
Plumbing / Hydraulic / Active Fire
Service
Insulated Copper Pipe
Fire Rating
120

Fire-stopping products

BF-3361-2 system drawing

Application dimensions

Min Diameter
15 mm
Max Diameter
15 mm
Service Diameter Range
15 mm
Aperture
61 mm
Sealant Depth
26 mm

Specimen size & details

15 mm copper pipe with 13 mm thick nitrile rubber insulation penetrating a 61 mm aperture. BOSS FireMastic-HPE™ sealant 26 mm deep in annular gap finished flush both sides.

Resources