BF-3431-5
System details
- Type
- Service Penetration
- Element
- Wall
- Substrate
- Masonry
- Minimum Substrate Thickness
- 100 mm
- FRL / FRR
- -/120/30
- Trade
- Electrical
- Service
- Multicore / Mains / Orange Circular
- Fire Rating
- 120
Fire-stopping products
Application dimensions
- Aperture
- 25 x 25 mm
Specimen size & details
Single 1 x 95 mm², PVC/PVC sheathed power cable. Cable installed in a 25 mm x 25 mm aperture protected by BOSS PenoPatch™ 60mm on both sides.