BF-3449-2

System details

Type
Service Penetration
Element
Wall
Substrate
Double Layer
Minimum Substrate Thickness
118 mm
FRL / FRR
-/60/60
Trade
Electrical
Service
TPS
Fire Rating
60

Fire-stopping products

BF-3449-2 system drawing

Application dimensions

Aperture
25 mm

Specimen size & details

1 - Sided penetration - Approved from both directions.
Bundle of up to 3 x 2.5 mm², 2C+E TPS Power Cables.
Cable bundle installed in a 25 mm aperture protected by BOSS PenoPatch™ 60mm at all penetration locations.