BF-3257-4

System details

Type
Service Penetration
Element
Wall
Substrate
Concrete
Minimum Substrate Thickness
118 mm
FRL / FRR
-/30/30
Trade
Plumbing / Hydraulic / Active Fire
Service
PEX

Fire-stopping products

BF-3257-4 system drawing

Application dimensions

Min Diameter
25 mm
Max Diameter
25 mm
Service Diameter Range
25 mm
Aperture
70.1 mm
Annular Gap
7.5 - 11.6 mm
Sealant Depth
13 mm

Specimen size & details

25 mm PEX pipe with 2.95 mm wall thickness, insulated with 13 mm thick nitrile insulation. BOSS FireMastic-HPE™ sealant 13 mm deep in annular gap finished flush both sides.