BF-3261-4

System details

Type
Service Penetration
Element
Wall
Substrate
Concrete
Minimum Substrate Thickness
118 mm
FRL / FRR
-/60/60
Trade
Plumbing / Hydraulic / Active Fire
Service
UPVC
Fire Rating
60

Fire-stopping products

BF-3261-4 system drawing

Application dimensions

Min Diameter
20 mm
Max Diameter
32 mm
Service Diameter Range
20, 25 and 32 mm
Aperture
70.1 mm
Sealant Depth
13 mm

Specimen size & details

uPVC conduit bundle incorporating 1 x 20 mm, 1 x 25 mm and 1 x 32 mm diameter conduits. BOSS FireMastic-HPE™ sealant 13 mm deep in the annular gap finished flush both sides.