BF-3263-4
System details
- Type
- Service Penetration
- Element
- Wall
- Substrate
- Concrete
- Minimum Substrate Thickness
- 118 mm
- FRL / FRR
- -/60/60
- Trade
- Electrical
- Service
- Aluminium Core
- Fire Rating
- 60
Fire-stopping products
Application dimensions
- Aperture
- 29 mm
- Annular Gap
- 4.1 - 7.9 mm
- Sealant Depth
- 13 mm
Specimen size & details
Nexans Cable - 16.95 mm diameter, 95 mm2 1C AL/PVC/XLPE electrical cable. BOSS FireMastic-HPE™ sealant 13 mm deep in annular gap finished flush both sides.