BF-3269-2

System details

Type
Service Penetration
Element
Wall
Substrate
Double Layer
Minimum Substrate Thickness
118 mm
FRL / FRR
-/60/60
Trade
HVAC
Service
HVAC Bundles
Fire Rating
60

Fire-stopping products

BF-3269-2 system drawing

Application dimensions

Aperture
137.4 mm
Annular Gap
2.1 - 10.4 mm
Sealant Depth
Fill collar mm

Specimen size & details

HVAC Bundle:
• 2 x 19.05 mm + 9.52 mm Paircoil with 19 mm insulation
• 2 x 2C 1.5 mm2 Control cable
• 2 x 2C + E 2.5 mm2 TPS cable
• 2 x 20 mm x 2.0 mm wall thickness uPVC Condensate drain.
A 150 mm BOSS MaxiCollar™ (Shell only) to both sides of the wall. BOSS FireMastic-HPE™ sealant to the full depth of the collar around the services, finished flush with the surface of the collar.