BF-3397-25
System details
- Type
- Service Penetration
- Element
- Floor
- Substrate
- Concrete Slab
- Minimum Substrate Thickness
- 120 mm
- FRL / FRR
- -/120/90
- Trade
- Electrical
- Service
- TPS
- Fire Rating
- 120
Fire-stopping products
Application dimensions
- Aperture
- 111 mm
- Sealant Depth
- 20 mm
Specimen size & details
Bundle of electrical and communications cables, including:
• 10 x 0.75 mm² Fire Alarm cables
• 20 x CAT6 cables
• 15 x 2.5 mm², 2C+E TPS power cables
• 4 x 16 mm² electrical cables
• 6 x COAX cables
• 70 mm² Aluminimum core electrical cable.
100 mm uPVC pipe cast into the concrete slab, flush with the top and bottom. BOSS FireMastic-HPE™ sealant 20 mm deep in annular gap finished flush with the bottom.